cleanroom, cleanrooms, laminar air flow, biotechnology,lab equipments,operation theatre laminar air flow, filters, calibration, biotech, tissue culture, air curtains, pharma industry cleanroom, cleanrooms, laminar air flow, biotechnology,lab equipments,operation theatre laminar air flow, filters, calibration, biotech, tissue culture, air curtains, pharma industry cleanroom, cleanrooms, laminar air flow, biotechnology,lab equipments,operation theatre laminar air flow, filters, calibration, biotech, tissue culture, air curtains, pharma industry cleanroom, cleanrooms, laminar air flow, biotechnology,lab equipments,operation theatre laminar air flow, filters, calibration, biotech, tissue culture, air curtains, pharma industry cleanroom, cleanrooms, laminar air flow, biotechnology,lab equipments,operation theatre laminar air flow, filters, calibration, biotech, tissue culture, air curtains, pharma industry
cleanroom
cleanroom, cleanrooms, laminar air flow, biotechnology,lab equipments,operation theatre laminar air flow, filters, calibration, biotech, tissue culture, air curtains, pharma industry

Airtech approaches each cleanroom design with a straightforward yet proven method in cleanroom principles. Whether you already have a preliminary drawing or need complete clean room design services, we can provide you with a cost effective system that meets your needs. All modular cleanrooms are designed in accordance with the appropriate clean room standard ISO 14644-1 / US Fed Std 209 as part of the overall clean room design service. Modular prefabricated clean rooms are factory engineered and designed to meet all your specifications for temperature, humidity, differential pressure, lighting, and noise levels. Our proprietary wall system can be designed and engineered to accommodate roof loads for storage or mechanical and process equipment.

Cleanroom Design Services

  • Licensed General Contractor
  • Engineering
  • On-Site Management To Save You Cost
  • Architectural Design
  • Structural Design
  • Electrical
  • HVAC
    Cleanroom Design Options
  • Class 1 through Class 100,000 to meet Federal STD. 209E / ISO14644-1
  • Temperature Control
  • Humidity Control
  • cleanroom design
    cleanroom design
    Cleanroom Design Guidelines
    SI
    ISO 14644-1
    Room Class
    Maximum allowable count per cubic foot of air.
    0.1p
    0.2p
    0.3p
    0.5p
    5p
     
    Class 1
               
    M1
    Class 2
    0
             
    M1.5
    Class 3
    1
    35
    7.5
    3
    1
     
    M2.5
    Class 4
    10
    350
    75
    30
    10
     
    M3.5
    Class 5
    100
     
    750
    300
    100
     
    M4.5
    Class 6
    1000
         
    1000
    7
    M5.5
    Class 7
    10,000
         
    10000
    70
    M6.5
    Class 8
    100,000
         
    100000
    700


    All Guidelines and Criteria are approximates
    CRITERIA
    CLASS 10 M2.5
    ISO 4
    CLASS 100 M3.5 ISO 5
    CLASS 1,000 M4.5 ISO 6
    CLASS 10,000 M5.5
    ISO 7
    CLASS 100,000 M5.5
    ISO 8
    Air Changes Per Hr / Min
    Per Hour/Per Minute   500-600/8-10
    300 To 480
    5 To 8
    180/3
    60/1
    30/.5
    Filter Coverage %
    90 to 100
    50 to 70
    20 to 30
    7 to 15
    4 to 5
    CFM Per Square Foot
    85 to 90
    36 to 65
    18 to 32
    9 to 16
    4 to 8
    Filter Efficiency
    99.9997
    (5-9s ULPAs)
    99.997
    (4-9s HEPAs)
    99.997
    (4-9s HEPAs)
    99.997
    (4-9s HEPAs)
    99.97
    (3-9s HEPAs)
    Type of Ceiling
    2" Aluminum Painted Grid
    2" Aluminum Painted Grid
    2" Aluminum Painted Grid
    1 1/2" T-Bar Conventional
    1 1/2" T-Bar Conventional
    Light Fixture Type
    Tear Drop or
    Flow Thru
    Tear Drop or 2'x4' C/R Fixture
    2' X 4' Cleanroom Fixture
    2' X 4' Cleanroom Fixture
    2' X 4' STD Fixture Field Sealed
    Ceiling Panels
    FRP or Epoxy Painted
    FRP, Vinylrock or Mylar
    Vinylrock or Mylar
    Vinylrock or Mylar
    Vinylrock or Mylar
    Wall System
    Modular
    Modular
    Modular
    Modular or Drywall
    Modular or Drywall
    Floor Covering
    Heat Weld Vinyl or Poured Epoxy
    Heat Welded Sheet Vinyl
    Solvent Welded Sheet Vinyl
    Sheet Vinyl or VCT
    Sheet Vinyl or VCT
    Flooring Base
    2" to 6' Cove
    Cove or Aluminum Base Channel
    Cove or Aluminum Base Channel
    Cove or Aluminum Base Channel
    Cove or Aluminum Base Channel
    Air Returns
    Raised Floor or Center Returns
    Low Wall on Long Axis
    Low Wall at Perimeter
    Low Wall
    Low Wall or Ceiling